CWG-16HEA454

产品简介

This Sentry PIPS CDU combines all of the features of a Switched CDU with the ability to provide power monitoring per inlet/infeed. Power information per infeed includes current, voltage, power, apparent power, crest factor, reactance, power factor and accumulated energy. This information replaces branch circuit monitoring devices typically installed in the power distribution panel or remote power panel (RPP) with higher accuracy and lower cost monitoring of each circuit attached to the CDU.

Also included in the Sentry POPS (Per Outlet Power Sensing) Switched CWG-16H2A454 CDU™ is network and serial-based power monitoring and alerting capabilities of the Switched Cabinet CDU plus the ability to monitor:

Current Load (A)
Voltage (V)
Power (W)
Apparent Power(VA)
Crest Factor and
Power Factor

Utilizing our grouping feature, power information is available per device (multiple outlets), groups of devices (applications), individual Cabinet PDU, cabinet, rows of cabinets or the whole Data Center Floor. Combine the Sentry POPS Switched Cabinet PDU with the Sentry Power Manager (SPM) software tool to cluster outlets and gain power usage information across multiple Cabinet PDU's individual IP address.

The Sentry Power Manager (SPM) provides power distribution unit power (kW and kW-h) monitoring and environmental monitoring across all Sentry CDU's within the network.  Reboot a single or dual-power supply server with one command.  Receive email alerts when power or environmental conditions exceed thresholds.  Assign users specific access rights to designated outlets or groups.  Only the Sentry Power Manager is capable of regulating all Sentry Cabinet PDU's across the network while providing power readings and management at an outlet level.

产品特点

Sentry Cabinet PDU Specifications
Item #Available Input
Voltages
Rated AmperageAvailable Input CordOutletsDimensions
(L x W x D)
CWG-16V(C13-C19)
CWG-16H2A454
CXG-16H2A454*
208 V-240 V
50/60Hz
20AIEC 60320/C20
Power Inlet
(16) IEC 60320/C133.50x17.00x7.00 in.
(89x432x178 mm)
CWG-16H2C454
CXG-16H2C454*
208 V-240 V
50/60Hz
30ANEMA L6-30P
Cord set, 10 ft (3m)
(16) IEC 60320/C133.50x17.00x7.00 in.
(89x432x178 mm)
CWG-16HEA454
CXG-16HEA454*
230V
50/60Hz
16AIEC 60320/C20
Power Inlet
(16) IEC 60320/C133.50x17.00x7.00 in.
(89x432x178 mm)
CWG-16HEK454
CXG-16HEK454*
230V
50/60Hz
32AIEC 60309
Cord set, 10 ft (3m)
(16) IEC 60320/C133.50x17.00x7.00 in.
(89x432x178 mm)
* CXG refers to the Expansion Module
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P (20A Twist-Lock) 10'(3m)
> PTCORD-2 IEC 60320/C19 - Schuko 10'(3m)
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 16/20A Blue (UK Commando) 10'(3m)
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10'(3m)
Additional Features and Specifications
Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS – EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024, CISPR 22 Class A

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2 and v3
> SSHv2
> Telnet
> LDAPv3/LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)
> IPv4 and v6

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe
   - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
   - EMCU-1-1B add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and
     1 water sensor port