产品简介
The Sentry 48DCWB-10-2X300-E0 Intelligent PDU and Remote Power Manager minimizes the impact of locked-up routers, servers and other network devices on business-critical networks. CLECs, ILECs, ISPs and enterprises use the Sentry 48DCWB-10-2X300-E0 to manage equipment in remote sites, co-location facilities and network operation centers. Sentry 48DCWB-10-2X300-E0 eliminates the need to dispatch a field service technician for manual intervention when devices lock-up. Using a Sentry 48DCWB-10-2X300-E0, the network operations center can quickly restart locked-up remote network servers to ensure that the network is fully operational around the clock.
Sentry 48 VDC PDUs provide immediate operational cost savings, including:
> Reduced field service visits
> Improved problem/solution response time
> Improved network availability
> Improved facility security
Eliminate the Need for a Separate Power Distribution Panel
> The Sentry 48DCWB-10-2X300-E0 is an intelligent unit that combines the functions of a power distribution panel and remote power management unit into a 3U 19"rack-mounted enclosure.
> Ten output terminal connections (five per input) are rated to switch 125 amps. Each outlet is protected by interchangeable TPC fuses or circuit breakers allowing for the current rating to be adjusted onsite.
Measurement Features
> Use RS-232 and/or TCP/IP to monitor the status of key measurement values. Receive SNMP or email alerts as well as Syslog when a measurement value is out of a predefined threshold.
Input Feed/Outlet "On Sense" - Verifies power at each power input/outlet connection.
Load Sense - Provides an accurate, real time measurement of the current draw, in amps, for each power outlet.
Environmental Sensors - Supports two external probes that each measure temperature and humidity.
产品特点
Sentry Cabinet PDU Specifications | |||||
Item # | Inputs | Rated Amperage | Low Current Outputs | High Current Outputs | Dimensions (W x H x D) |
-48V Switched 2x300A Inputs / 10x125A Outputs | |||||
48DCWB-10-2X300-E0 48DCXB-10-2X300-E0* | (2) -48VDC (-40 to -60) Input Terminal | 300A each, 600A total | None | (10) 125A max outlets protected with TPC fuses or breakers | 3U, 5.25 x 17.0 x 20.0 in. (133 x 432 x 508 mm)** |
*Expansion PDU **Dimensions exclude the 19” standard mounting brackets included with PDU | |||||
Circuit Protection Options (must be ordered with unit) | |||||
> CB-0005-100G (100A Bullet Style Circuit Breaker) > FUSE-TPC-100 (100A TPC Fuse) > FUSE-TPC-125 (125A TPC Fuse) (consult server technology for other circuit protection options) > KIT-0063 (Breaker Mounting Kit - One per CDU when ordered with breakers) > KIT-0064 (Fuse Mounting Kit - One per CDU when ordered with fuses) | |||||
Optional Accessories | |||||
> EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m) > EMCU-1-1B Environmental Monitor adding - Two (2) EMTH-1-1 Temperature/Humidity Probes (one included) - One (1) EMWS-1-1 Water Sensor (sold separately) - Four (4) Dry Contact (NO/NC) monitoring points - One (1) 8-bit analog-to-digital converter (0 to 5VDC) > SPM (Sentry Power Manager) - Monitor and manage multiple PDUs from a single point - Monitor and manage alarm conditions - Create reports and trends on stored data - Control and analyze power usage per power supply and device - Optional appliance or virtual version - VMware READY | |||||
Certifications | |||||
> US & Canada (cTUVus Mark) to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07 > EU (TUVGS Mark) to EN 60950-1:2006 +A11 > CE Mark | |||||
Communications and Security | |||||
> HTTP/HTTPS > SSLv3/TLSv1 > SNMPv2c & v3 > SSHv2 > Telnet > LDAPS/LDAPv3 > TACACS+ > RADIUS > RS-232 (Serial) |