产品简介
The Server Technology® C-16HF1 Fail-Safe Transfer Switch (FSTS)provides fail-over redundancy to single or dual power supply servers andnetwork devices. Exclusive to the Fail-Safe Transfer Switch is its abilityto carry loads on both the A and B circuits during normal operation.
Unlike a common automatic transfer switch, theFail-Safe unit is unique in that the "A" in-feed routinely powers halfthe outlets, and the "B" in-feed routinely powers the other half.However, if either in-feed goes down, the other powers all outlets. This"Fail-Safe" method has several advantages compared to a standard ATS.A standard ATS contains two-in-feeds, but runs all outlets from just onesource, with the secondary source only being used once an outage occurs. The ServerTechnology design does not prohibit load balancing between the two suppliedcircuits which results in less heat and a lower voltage drop compared to thesame load existing on just one source. Only when an outage occurs on one of thetwo sources will the entire load be applied to a single source.产品特点
Sentry Cabinet PDU Specifications | |||||
Model # | Connector | Cord | Current Rating | Voltage Rating | |
Rack Mount Fail-Safe Transfer Switch CDU | |||||
C-16HF1-C20 | IECC20 | UsePTCORD* | ≤16A (20A max) | 100V-120VL-N nominal, 60Hz | |
C-16HF1-L30 | NEMAL5-30P | 10ft,3-conductor, 10AWG | ≤24A (30A max) | 100V-120VL-N nominal, 60Hz | |
*PTCORD'sordered separately. Choose L6-20P, L5-20P, CEE 7/7 Schuko, IEC 60309 2P+E, orBS1363 | |||||
Additional Features and Specifications | |||||
Standards > cTUVus – UL 60950-1:2007 > CAN/CSA 22.2 No. 60950-1-07 > FCC Class A, Part 15 | Branch Circuit Protection >Compliant to UL 60905-1 | ||||
Input Power > Dual Power Source Input > Each input supplies power to half of the outlets > Input power cables for NEMA L5-30P, L6-30P, IEC 60390/C19 Indicator LEDs >Monitor load per circuit | Voltage Range > 100-120V (configurable) > Inputs must have same voltage UPS Compatibility > Transfer Switch is compatible with a UPS that provides a sin wave AC output waveform Transfer Rate > Power transfer in 10-16 milliseconds maximum |
Output | |||||
Model # | Outlets | Current Rating | Usable | Max Power | |
North America | |||||
C-16HF1-C20 | (16)NEMA 5-20R | ≤16A (20A max) | 1.9kW | 2.4kW@120V | |
C-16HF1-L30 | (16)NEMA 5-20R | ≤16A (20A max) | 2.8kW | 3.6kW@120V |