The Server Technology® C-16HF2/E Fail-Safe Transfer Switch (FSTS) provides fail-over redundancy to single or dual power supply servers and network devices. Exclusive to the Fail-Safe Transfer Switch is its ability to carry loads on both the A and B circuits during normal operation.Unlike a common automatic transfer switch, the Fail-Safe unit is unique in that the "A" in-feed routinely powers half the outlets, and the "B" in-feed routinely powers the other half. However, if either in-feed goes down, the other powers all outlets. This "Fail-Safe" method has several advantages compared to a standard ATS. A standard ATS contains two-in-feeds, but runs all outlets from just one source, with the secondary source only being used once an outage occurs. The Server Technology design does not prohibit load balancing between the two supplied circuits which results in less heat and a lower voltage drop compared to the same load existing on just one source. Only when an outage occurs on one of the two sources will the entire load be applied to a single source.

产品特点

Sentry  Cabinet PDU Specifications
Model #ConnectorCordCurrent Rating
Voltage Rating
Rack Mount Fail-Safe Transfer Switch CDU
C-16HF2-C20
IEC C20
Use PTCORD*
≤ 16A (20A max)
208V-240V L-L nominal, 60Hz
C-16HF2-L30
NEMA L6-30P
10ft, 3-conductor, 10AWG
≤ 24A (30A max)
208V-240V L-L nominal, 60Hz
C-16HFE-C20
IEC C20
Use PTCORD*
≤ 16A
220V-240V L-N nominal, 50Hz
C-16HFE-P32
IEC 60309 6hr
2P+PE Blue Plug
3m, 3-conductor, H05VV-F, 4.0mm²
≤ 32A
220V-240V L-N nominal, 50Hz
*PTCORD'sordered separately. Choose L6-20P, L5-20P, CEE 7/7 Schuko, IEC 60309 2P+E, orBS1363
Additional Features and Specifications
Standards
> cTUVus – UL 60950-1:2007
> CAN/CSA 22.2 No. 60950-1-07
> TUVGS – EN 60950-1:2006
> FCC Class A, Part 15
Branch Circuit Protection
>Compliant to UL 60905-1
Input Power
> Dual Power Source Input
> Each input supplies power to half of the outlets
> Input power cables for NEMA L5-30P, L6-30P, IEC 60390/C19

Indicator LEDs
>Monitor load per circuit
Voltage Range
> 208-240V (configurable)
> Inputs must have same voltage

UPS Compatibility
> Transfer Switch is compatible with a UPS that provides a sin wave AC output waveform

Transfer Rate
> Power transfer in 10-16 milliseconds maximum

Output
Model #OutletsCurrent Rating
Usable
Max Power
North America
C-16HF2-C20
(16) IEC C13
≤ 12A (15A max)
3.3kW
4.1kW @208V
C-16HF2-L30
(16) IEC C13
≤ 12A (15A max)
5.0kW
6.2kW @208V
Global
C-16HFE-C20
(16) IEC C13
≤ 10A
-
3680W @230V
C-16HFE-P32
(16) IEC C13
≤ 10A
-
7360W @230V