The Server Technology® C-16HF2/E Fail-Safe Transfer Switch (FSTS) provides fail-over redundancy to single or dual power supply servers and network devices. Exclusive to the Fail-Safe Transfer Switch is its ability to carry loads on both the A and B circuits during normal operation.Unlike a common automatic transfer switch, the Fail-Safe unit is unique in that the "A" in-feed routinely powers half the outlets, and the "B" in-feed routinely powers the other half. However, if either in-feed goes down, the other powers all outlets. This "Fail-Safe" method has several advantages compared to a standard ATS. A standard ATS contains two-in-feeds, but runs all outlets from just one source, with the secondary source only being used once an outage occurs. The Server Technology design does not prohibit load balancing between the two supplied circuits which results in less heat and a lower voltage drop compared to the same load existing on just one source. Only when an outage occurs on one of the two sources will the entire load be applied to a single source.
产品特点
Sentry Cabinet PDU Specifications | |||||
Model # | Connector | Cord | Current Rating | Voltage Rating | |
Rack Mount Fail-Safe Transfer Switch CDU | |||||
C-16HF2-C20 | IEC C20 | Use PTCORD* | ≤ 16A (20A max) | 208V-240V L-L nominal, 60Hz | |
C-16HF2-L30 | NEMA L6-30P | 10ft, 3-conductor, 10AWG | ≤ 24A (30A max) | 208V-240V L-L nominal, 60Hz | |
C-16HFE-C20 | IEC C20 | Use PTCORD* | ≤ 16A | 220V-240V L-N nominal, 50Hz | |
C-16HFE-P32 | IEC 60309 6hr 2P+PE Blue Plug | 3m, 3-conductor, H05VV-F, 4.0mm² | ≤ 32A | 220V-240V L-N nominal, 50Hz | |
*PTCORD'sordered separately. Choose L6-20P, L5-20P, CEE 7/7 Schuko, IEC 60309 2P+E, orBS1363 | |||||
Additional Features and Specifications | |||||
Standards > cTUVus – UL 60950-1:2007 > CAN/CSA 22.2 No. 60950-1-07 > TUVGS – EN 60950-1:2006 > FCC Class A, Part 15 | Branch Circuit Protection >Compliant to UL 60905-1 | ||||
Input Power > Dual Power Source Input > Each input supplies power to half of the outlets > Input power cables for NEMA L5-30P, L6-30P, IEC 60390/C19 Indicator LEDs >Monitor load per circuit | Voltage Range > 208-240V (configurable) > Inputs must have same voltage UPS Compatibility > Transfer Switch is compatible with a UPS that provides a sin wave AC output waveform Transfer Rate > Power transfer in 10-16 milliseconds maximum |
Output | |||||
Model # | Outlets | Current Rating | Usable | Max Power | |
North America | |||||
C-16HF2-C20 | (16) IEC C13 | ≤ 12A (15A max) | 3.3kW | 4.1kW @208V | |
C-16HF2-L30 | (16) IEC C13 | ≤ 12A (15A max) | 5.0kW | 6.2kW @208V | |
Global | |||||
C-16HFE-C20 | (16) IEC C13 | ≤ 10A | - | 3680W @230V | |
C-16HFE-P32 | (16) IEC C13 | ≤ 10A | - | 7360W @230V |