产品简介
The Sentry CW-16HF2/E Fail-SafeTM provides fail-over redundancy to single or dual-power supply servers and network devices. Exclusive to the Sentry Switched Fail-Safe is its ability to carry loads on the A circuit, B circuit or both and to remotely manage the outlets.
Similar, but unlike a common automatic transfer switch, the Sentry Switched Fail-Safe unit is unique in that it contains two (2) in-feeds and two (2) banks of eight (8) outlets each, for a total of 16 outlets across the two circuits.
The "A" in-feed routinely powers just the A1-8 outlets, and the "B" in-feed routinely powers just the B1-8 outlets. However, if the "A" in-feed goes down, the "B" in-feed powers all 16 outlets and the same if the "B" in-feed goes down, the "A" in-feed powers all the outlets.
This new "Fail-Safe" method has several advantages compared to a standard ATS because it does not prohibit load balancing between the two supplied circuits. A standard ATS contains two-in-feeds, but runs all outlets from just one source, with the secondary source only being used once an outage occurs on the capacity. This results in less heat, less resistance, and consequently less of a voltage drop compared to the same load existing on just one source. Only when an outage occurs on one of the two sources will the entire load be applied to a single source.
产品特点
Sentry Cabinet PDU Specifications | |||||
Item # | Available Input Voltages | Rated Amperage | Available Input Cord | Outlets | Dimensions (L x W x D) |
Fail-Safe CW-16HF2/E 208-240V | |||||
CW-16HF2A452 CX-16HF2A452* | 208-240V 50/60Hz | 20A | (2) IEC C20 Power Inlets | (16) IEC 60320/C13 | 17.2 x 3.50 x 10.0 in. (437 x 89 x 254 mm) |
CW-16HF2C452 CX-16HF2C452* | 208-240V 50/60Hz | 30A | (2) NEMA L6-30P Plugs, 10'(3m) Cord | (16) IEC 60320/C13 | 17.2 x 3.50 x 10.0 in. (437 x 89 x 254 mm) |
CW-16HFEA452 CX-16HFEA452* | 230V 50/60Hz | 16A | (2) IEC C20 Power Inlets | (16) IEC 60320/C13 | 17.2 x 3.50 x 10.0 in. (437 x 89 x 254 mm) |
CW-16HFEK452 CX-16HFEK452* | 230V 50/60Hz | 32A | (2) IEC Blue 2P+G Plug, 10'(3m) Cord | (16) IEC 60320/C13 | 17.2 x 3.50 x 10.0 in. (437 x 89 x 254 mm) |
*Indicates Expansion Unit | |||||
Power Cord Options | |||||
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P (20A Twist-Lock) 10?(3m) > PTCORD-2 IEC 60320/C19 - Schuko 10?(3m) > PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 16/20A Blue (UK Commando) 10?(3m) > PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10?(3m) | |||||
Additional Features and Specifications | |||||
Standards > cTUVus ? UL 60950-1-2003 > CAN/CSA 22.2 No. 60950-1:2003 > TUVGS ? EN 60950-1:2001 > FCC Class A, Part 15 > CE > EMC-EN 55022 Class A, EN 55024 Communications > 10/100 BaseT Ethernet > HTTP/HTTPS > SSLv3/TLSv1 > SNMPv2 > SSHv2 > Telnet > LDAPv3/LDAPS > TACACS+ > RS-232 (Serial) Branch Circuit Protection > Compliant to UL 60905-1 Accessories > Temperature & Humidity Probe - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m) - EMCU-1-1B add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and 1 water sensor port - EMWS-1-1 Water Sensor |