产品详情
C-24VY-L30MA

产品简介

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet PDU. The Sentry Cabinet PDU product family uniquely meets these demands.

The Sentry Cabinet Power Distribution Unit (CDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the Cabinet PDU's True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.

The Cabinet PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes a Bussman® SC fuse as an Overcurrent Protection Device (OCPD). Now you can safely run 30-amp power drops to your server cabinet where individual outlet receptacles have lower output ratings (i.e., 20-amps)

产品特点


Sentry CDU Specifications
Item #Available Input
Voltages

Rated

Amperage

Available Input CordOutletsDimensions*
(L x W x D)
C-24VD/VY(C13/C19)-3Ph
C-24VD-L30MA3-Phase Delta,
208V 50/60Hz
30ANEMA L15-30P
Cordset, 10 ft (3m)
(18) IEC 60320/C13
(6) IEC 60320/C19
69" x 1.75" x 2.25"
(1753 x44.4x57mm)
C-24VY-L30MA3-Phase Wye,
208V 50/60Hz
30ANEMA L21-30P
Cordset, 10 ft (3m)
(18) IEC 60320/C13
(6) IEC 60320/C19
69" x 1.75" x 2.25"
(1753 x44.4x57mm)
* Please note that the depth of these enclosures are 3.0" deep at the placement of the fuse retractors.
Additional Features and Specifications
Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS – EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Branch Circuit Protection
> Compliant to UL 60950-1