产品详情
CS-16V2-L30M

产品简介

he Smart Cabinet PDU delivers reliable power distribution, local power monitoring via LEDs, power monitoring via IP and environmental (temperature & humidity) monitoring via IP.  

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet PDU.  The Sentry CDU product family uniquely meets these demands.

The Sentry Cabinet Power Distribution Unit (CDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the Cabinet PDU's True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.  

The Cabinet PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes a Bussman® SC fuse as an Overcurrent Protection Device (OCPD).  

230 V products include a EN 60950-1:2001 certification.

产品特点


Sentry  Cabinet PDU Specifications
Item #Available Input
Voltages

Rated

Amperage

Available Input CordOutletsDimensions
(L x W x D)*
CW-16V
CS-16V2-C20M
CL-16V2-C20M*
208-240V
50/60Hz
20AIEC 60320/C20
Power Inlet
(16) IEC 60320/C1349.50"x1.75"x2.25"
(1257x44.4x57mm)
CS-16V2-L30M
CL-16V2-L30M*
208-240V
50/60Hz
30ANEMA L6-30P
Cord Set, 10 ft (3m)
(16) IEC 60320/C1349.50"x1.75"x2.25"
(1257x44.4x57mm)
CS-16VE-C20M
CL-16VE-C20M*
230V
50/60Hz
16AIEC 60320/C20
Power Inlet
(16) IEC 60320/C1349.50"x1.75"x2.25"
(1257x44.4x57mm)
CS-16VE-P32M
CL-16VE-P32M*
230V
50/60Hz
32AIEC 60309
Cord Set
(16) IEC 60320/C1349.50"x1.75"x2.25"
(1257x44.4x57mm)
* CL refers to the Expansion Module
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P (20A Twist-Lock) 10'
> PTCORD-2 IEC 60320/C19 - Schuko 10'
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 16/20A Blue (UK Commando) 10'
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10'
Additional Features and Specifications

Standards
> cTUVus – UL 60950-1-2007
> CAN/CSA 22.2 No. 60950-1:2007 + A11
> TUVGS – EN 60950-1:2007
> FCC Class A, Part 15
> CE Mark
> EMC-EN 55022 Class A, EN 55024, CISPR 22 Class A

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2 and v3
> Telnet
> LDAPv3/LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)
> IPv4 and IPv6

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe
   - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)