产品详情
CL-24VDV454-006


产品简介

The Smart Cabinet PDU delivers reliable power distribution, individual branch monitoring via LEDs, power monitoring via IP and environmental (temperature & humidity) monitoring via IP. Top power cord entry provides an ideal solution for overhead busway power to the rack.

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet rack PDU. The Sentry cabinet PDU  product family uniquely meets these demands.

The Sentry Cabinet Power Distribution Unit (CDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the Cabinet PDUs True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.

The PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes circuit breakers as an Overcurrent Protection Device (OCPD).

产品特点


Sentry Cabinet PDU Specifications
Item #Available Input
Voltages

Rated

Amperage

Available Input CordOutletsDimensions
(L x W x D)
CS-24VD/VY-3Ph
CS-24VDX454-006
CL-24VDX454-006*
3-Phase Delta, 240V50/60Hz60AIEC 60309 Cord Set, 10ft(3m)(12)  IEC 60320/C13 & (12) IEC 60320/C1969.0"x1.75"x3.50"
(1752x44x89mm)
CS-24VDV454-006
CL-24VDV454-006*
3-Phase Delta, 240V50/60Hz50ACS8365C, Cord Set, 10ft (3m)(12)  IEC 60320/C13 & (12) IEC 60320/C1969.0"x1.75"x3.50"
(1752x44x89mm)
CS-24VYY454-006
CL-24VYY454-006*
3-Phase Wye, 208V50/60Hz60AIEC 60309  Cordset, 10ft (3m)(12)  IEC 60320/C13 & (12) IEC 60320/C1969.0"x1.75"x3.50"
(1752x44x89mm)
*CL refers to the Expansion Module
Additional Features and Specifications
Standards
> cTUVus - UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS - EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3/LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60905-1

Accessories
> EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
> EMCU-1-1B allows up to (2) additional temperature & humidity probes, (1) water sensor, (4) dry contact closures, (1) analog-to-digital contact sensor. Includes (1) temperature/humidity probe with unit.
> Sentry Power Manager (SPM)