产品详情
CS-12HYM444C8

产品简介

The Sentry CS-12HD/HY products provide both C13 and C19 outlets for high density applications found in data center cabinets. Smart Cabinet Distribution Units (CDU) provide reliable 3-phase power distribution combined with local and remote power monitoring and environmental monitoring via IP.

This Sentry PIPS CDU combines all of the features of a Smart CDU with the ability to provide power monitoring per inlet/infeed. Power information per infeed includes current, voltage, power, apparent power, crest factor, reactance, power factor and accumulated energy. This information replaces branch circuit monitoring devices typically installed in the power distribution panel or remote power panel (RPP) with higher accuracy and lower cost monitoring of each circuit attached to the CDU.

Combine the Sentry PIPS Smart Cabinet PDU with the Sentry Power Manager (SPM) software tool to gain power usage information across multiple Cabinet PDU's individual IP address.

This Smart cabinet PDU delivers reliable power distribution, local power monitoring via LEDs, power monitoring via IP and environmental (temperature & humidity) monitoring via IP.

The Sentry Cabinet Power Distribution Unit (CDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the Cabinet PDUs True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.

The PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes circuit breakers (UL-489 rated circuit breakers) as an Overcurrent Protection Device (OCPD).

产品特点


Sentry  Cabinet PDU Specifications
Item #Available Input
Voltages

Rated

Amperage

Available Input CordOutletsDimensions
(L x W x D)
CS-12HD/HY - 3Ph 20/30A 6xC13 & 6xC19
CS-12HDD444C8
CL-12HDD444C8*
240V 3-Phase Delta, 50/60 Hz20ANEMA L15-20P Plug, 10'(3m) Cord(6) IEC 60320/C13
(6) IEC 60320/C19
3.50 x 17.00 x 10.00 in.
(89 x 432 x 254 mm)
CS-12HDE444C8
CL-12HDE444C8*
240V 3-Phase Delta, 50/60 Hz30ANEMA L15-30P Plug, 10'(3m) Cord(6) IEC 60320/C13
(6) IEC 60320/C19
3.50 x 17.00 x 10.00 in.
(89 x 432 x 254 mm)
CS-12HYL444C8
CL-12HYL444C8*
208V 3-Phase Wye, 50/60 Hz20ANEMA L21-20P Plug, 10'(3m) Cord(6) IEC 60320/C13
(6) IEC 60320/C19
3.50 x 17.00 x 10.00 in.
(89 x 432 x 554 mm)
CS-12HYM444C8
CL-12HYM444C8*
208V 3-Phase Wye, 50/60 Hz30ANEMA L21-30P Plug, 10'(3m) Cord(6) IEC 60320/C13
(6) IEC 60320/C19
3.50 x 17.00 x 10.00 in.
(89 x 432 x 254 mm)
*CL refers to the Expansion Module
**Lacing bar adds 4 in. (102 mm) to depth when installed in rack
Additional Features and Specifications
Standards
> cTUVus ? UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> FCC Class A, Part 15
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3/LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60905-1

Accessories
> EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
> EMCU-1-1B allows up to (2) additional temperature & humidity probes, (1) water sensor, (4) dry contact closures, (1) analog-to-digital contact sensor. Includes (1) temperature/humidity probe with unit.
> Sentry Power Manager (SPM)