产品简介
The Sentry CS-15H products provide twelve IEC 60320 C19 and three IEC 60320 C13 outlets for high density applications found in data center cabinets. Smart Cabinet Distribution Units (CDU) provide reliable 3-phase power distribution combined with local and remote power monitoring and environmental monitoring via IP.
The Sentry CS-15H Cabinet Distribution Units (CDU) provide reliable 3-phase power distribution combined with local and remote power monitoring and environmental monitoring via IP. Use the network interface to view power, temperature, and humidity levels via Web browser, or receive SNMP-based alarms and email alerts when conditions exceed defined thresholds.
The Smart CDU family has the capability to daisy chain units together. The expansion CDU Module give the ability to use one IP address across different power circuits.
The PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes circuit breakers (UL-489 rated circuit breakers) as an Overcurrent Protection Device (OCPD).
产品特点
Sentry Cabinet PDU Specifications | |||||
Item # | Available Input Voltages | Rated Amperage | Available Input Cord | Outlets | Dimensions** (L x W x D) |
CS-15H4 230/400V | |||||
CS-15H4J454C3-013 CL-15H4J454C3-013* | 230/400V 3-phase Wye,50/60Hz | 16A | IEC Red 6hr 3P+N+G Plug3m(10ft), Front Entry | (12) IEC 60320/C19 (3) IEC 60320/C13 | 3.50 x 17.0 x 14.0 in (89 x 432 x 356 mm) |
CS-15H4K454C3-013 CL-15H4K454C3-013* | 230/400V 3-phase Wye, 50/60Hz | 32A | IEC Red 6hr 3P+N+G Plug3m(10ft), Front Entry | (12) IEC 60320/C19 (3) IEC 60320/C13 | 3.50 x 17.0 x 14.0 in (89 x 432 x 356 mm) |
*CL refers to the Expansion Module ** Depth dimensions include mounting bracket and cable lacing rails. | |||||
Additional Features and Specifications | |||||
Standards > TUVGS Mark to EN 60950-1:2006 + A11 > EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A > FCC Class A, Part 15 > CE Mark > RoHS/WEEE Communications > 10/100 BaseT Ethernet > HTTP/HTTPS > SSLv3/TLSv1 > SNMPv2 and v3 > SSHv2 > Telnet > LDAPv3 > LDAPS > TACACS+ > RADIUS > RS-232 (Serial) > IPv4 & IPv6 Branch Circuit Protection > Compliant to UL 60905-1 Accessories > EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m) > EMCU-1-1B allows up to (2) additional temperature & humidity probes, (1) water sensor, (4) dry contact closures, (1) analog-to-digital contact sensor. Includes (1) temperature/humidity probe with unit. > Sentry Power Manager (SPM) |