产品详情
CS-2HD1A131Z1

产品简介

The dual input, dual output Smart Power Monitor allows the ability to easily add input current load and power monitoring to any existing cabinet via an integral web based interface or through a serial connection.

This allows you to determine:
1) if there is available power to add additional devices to the cabinet.
2) if you are close to exceeding the circuit's capacity potentially leading to an over current protection device tripping and bringing down the input feed.
3) if each CDU is properly loaded to ensure redundancy when one of the two input feeds is lost.

This product is perfect for cabinets with pre-existing 120V basic power strips that need to be upgraded to include monitoring capabilities.
Note: In an A and B power input-feed configuration, each Cabinet Power Distribution Unit (CDU) should not be loaded to over 40% of the rated capacity to ensure that if one of the two power feeds is lost that the whole load can be supported by the remaining CDU.


产品特点

Sentry  Cabinet PDU Specifications
Item #Input VoltagesRated
Amperage
InputsOutletsDimensions
(L x H x D)
CS-2HD1

CS-2HD1A131Z1

100 - 120V 50/60Hz

20A

(2) IEC 60320/C20 Power Inlets

(2) IEC 60320/C19 Outlets

1.75"x17.0"x10.0"
(44x432x254mm)
Additional Features and Specifications
Power Cord Options
> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10'
> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10'
> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10'

Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe
  - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)