产品简介
The dual input, dual output Smart Power Monitor allows the ability to easily add input current load and power monitoring to any existing cabinet via an integral web based interface or through a serial connection.
This allows you to determine:
1) if there is available power to add additional devices to the cabinet.
2) if you are close to exceeding the circuit's capacity potentially leading to an over current protection device tripping and bringing down the input feed.
3) if each CDU is properly loaded to ensure redundancy when one of the two input feeds is lost.
This product is perfect for large storage solutions like SAN's where the CS-2HD can be added to existing installations to determine the power draw of these systems.
Note: In an A and B power input-feed configuration, each Cabinet Power Distribution Unit (CDU) should not be loaded to over 40% of the rated capacity to ensure that if one of the two power feeds is lost that the whole load can be supported by the remaining CDU.
产品特点
Sentry Cabinet PDU Specifications | |||||
Item # | Input Voltages | Rated Amperage | Inputs | Outlets | Dimensions (L x H x D) |
CS-2HD2/HDE C19/C20 | |||||
CS-2HD2A131Z1 | 208-240V 50/60Hz | 20A | (2) IEC 60320/C20 Power Inlets | (2) IEC 60320/C19 Outlets | 1.75"x17.0"x10.0" (44x432x254mm) |
CS-2HDEA131Z1 | 230V 50/60 Hz | 16A | (2) IEC 60320/C20 Power Inlets | (2) IEC 60320/C19 Outlets | 1.75"x17.0"x10.0" (44x432x254mm) |
Additional Features and Specifications | |||||
Power Cord Options > PTCORD-1 IEC 60320/C19 - NEMA L6-20P (20A Twist-Lock) 10' > PTCORD-2 IEC 60320/C19 - Schuko 10' > PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 16/20A Blue (UK Commando) 10' > FCC Class A, Part 15 > PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10' Standards > cTUVus – UL 60950-1-2003 > CAN/CSA 22.2 No. 60950-1:2003 > TUVGS – EN 60950-1:2001 > FCC Class A, Part 15 > CE > EMC-EN 55022 Class A, EN 55024 Communications > 10/100 BaseT Ethernet > HTTP/HTTPS > SSLv3/TLSv1 > SNMPv2 > SSHv2 > Telnet > LDAPv3 and LDAPS > TACACS+ > RADIUS > RS-232 (Serial) Branch Circuit Protection > Compliant to UL 60950-1 Accessories > Temperature & Humidity Probe - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m) |