产品详情
CS-2HDYL131Z1

产品简介

The dual input, dual output Smart Power Monitor allows the ability to easily add input current load and power monitoring to any existing cabinet via an integral web based interface or through a serial connection.


This allows you to determine:
1) if there is available power to add additional devices to the cabinet.
2) if you are close to exceeding the circuit's capacity potentially leading to an over current protection device tripping and bringing down the input feed.
3) if each CDU is properly loaded to ensure redundancy when one of the two input feeds is lost.

This product is perfect for large storage solutions like SAN's where the CS-2HD can be added to existing installations to determine the power draw of these systems.
Note: In an A and B power input-feed configuration, each Cabinet Power Distribution Unit (CDU) should not be loaded to over 40% of the rated capacity to ensure that if one of the two power feeds is lost that the whole load can be supported by the remaining CDU.


产品特点

Sentry  Cabinet PDU Specifications
Item #Input
Voltages
Rated
Amperage
InputsOutputsDimensions
(L x H x D)
CS-2HDD/HDY-3Ph
CS-2HDDD131Z13-Phase Delta, 208V,
50/60 Hz
20A(2) NEMA L15-20P
Cord Set, 10ft (3.0m)
(2) NEMA L15-20R
Cord Set, 3ft (.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
CS-2HDDE131Z13-Phase Delta, 208V,
50/60 Hz
30A(2) NEMA L15-30P
Cord Set, 10ft (3.0m)
(2) NEMA L15-30R
Cord Set, 3ft (.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
CS-2HDYL131Z13-Phase Wye, 208V,
50/60 Hz
20A(2) NEMA L21-20P
Cord Set, 10ft (3.0m)
(2) NEMA L21-20R
Cord Set, 3ft (.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
CS-2HDYM131Z13-Phase Wye, 208V,
50/60 Hz
30A(2) NEMA L21-30P
Cord Set, 10ft (3.0m)
(2) NEMA L21-30R
Cord Set, 3ft (.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
Additional Features and Specifications
Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS – EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe
   - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)