CS-2HDDV131Z1-011

产品简介


The dual input, dual output Smart Power Monitor allows the ability to easily add input current load and power monitoring to any existing cabinet via an integral web based interface or through a serial connection.  This product is unique because it supports 3-Phase 208-240V, 50 and 60 Amp power feeds.  Now data center managers can easily add smart power monitoring intelligence to their existing high amperage cabinets without replacing their current CDUs.


This allows you to determine:
1) if there is available power to add additional devices to the cabinet.
2) if you are close to exceeding the circuit's capacity potentially leading to an over current protection device tripping and bringing down the input feed.
3) if each CDU is properly loaded to ensure redundancy when one of the two input feeds is lost.

This product is perfect for large storage solutions like SAN's where the CS-2HD can be added to existing installations to determine the power draw of these systems.
Note: In an A and B power input-feed configuration, each Cabinet Power Distribution Unit (CDU) should not be loaded to over 40% of the rated capacity to ensure that if one of the two power feeds is lost that the whole load can be supported by the remaining CDU.

产品特点

Sentry  Cabinet PDU Specifications
Item #Input VoltagesRated
Amperage
InputsOutletsDimensions
(H x W x D)
CS-2HDDX/DV
CS-2HDDV131Z13-Phase Delta,240V, 50/60Hz50A(2) CS8365C
Cord Set, 10ft (3m)
(2) CS8364C
Cord Set, 3ft (0.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
CS-2HDDV131Z1-0113-Phase Delta, 240V, 50/60Hz50A(2) Russell Stoll 9P54U2 Cord Set, 10ft (3m)(2) CS8364C
Cord Set, 3ft (0.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
CS-2HDDX131Z13-Phase Delta,240V, 50/60Hz60A(2) IEC 60309
Cord Set, 10ft (3m)
(2) IEC 60309
Cord Set, 3ft (0.9m)
1.75"x17.0"x10.0"
(44x432x254mm)
Additional Features and Specifications
Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe
  - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
> Sentry Power Manager (SPM)
  - Monitor and Manage multiple Sentry CDU's
  - Monitor and Manage all alarm conditions
  - Reporting and Trending
  - Group or Cluster outlets for reboot and power information
> Environmental Monitor
  -EMCU-1-1B allows up to (2) additional temperature & humidity probes, (1) water sensor, (4) dry contact closures, (1) analog-to-digital contact sensor. Includes (1) temperature/humidity probe with unit.