产品详情
C2W36CE- YCMFA966

产品简介

The Server Technology® PRO2 Switched CDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched "Master" CDU can be connected to as many as three PRO2 Switched "Link" CDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking configuration.

产品特点


Sentry  Cabinet PDU Specifications
Master CDU
Link CDUInput Current
Input Plug
Input Voltage
Rated Power
Global
C2W36CE-
DBMFA966
C2X36CE-
DBMFA966
≤16A
(20 peak)
NEMA L15-20P
10ft, 4-C, 12AWG
208V, L-L
50/60Hz
5.7kW @208V
C2W36CE-
DCMFA966
C2X36CE-
DCMFA966
≤24A
(30 peak)
NEMA L15-30P
10ft, 4-C, 10AWG
208V, L-L
50/60Hz
8.6kW @208V
C2W36CE-
YBMFA966
C2X36CE-
YBMFA966
≤16A
(20 peak)
NEMA L21-20P.
10ft, 5-C, 12AWG
120/208V, L-L
50/60Hz
5.7kW @208V
C2W36CE-
YCMFA966
C2X36CE-
YCMFA966
≤24A
(30 peak)
NEMA L21-30P
10ft, 5-C, 10AWG
120/208V, L-L
50/60Hz
8.6kW @208V
*Note: replace the 9 (front entry) with M for base entry cord.
Additional Features and Specifications
Outputs
• Connector: (24) x IEC 60320/C13
• North American Rating (C13): ≤ 12A @208V (15A peak)
• Connector: (12) x IEC 60320/C19
• North American Rating (C19): ≤ 16A @208V (20A peak)
• Connector: (3) x NEMA 5-15/20R (on L21 input designs only)
• North American Rating (5-15/20R): ≤ 16A @120V (20A peak)
• LockedIn™ compatible. Locking outlets provide high-retention even for non-locking cords

Input measurement accuracy
• LED Current = ± 10% 0.1 amp (0.3 – 9.9amps) and  1 amp (>9.9amps) resolution
• GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
• Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
• Active Power = ± 1% at 1 watt resolution
• Apparent Power = ± 1% at 1 volt-amp resolution
• Power Factor = ± 3% at 0.01 resolution
• Crest Factor = ± 10% at 0.1 resolution
• Energy = ± 1% at 0.1 kilowatt-hour resolution

Branch measurement accuracy
• Current = ± 3% at 0.01 amp resolution (above 0.5 amp)

Branch Circuit Protection
• UL489 compliant 2-pole, 20A trip circuit breakers, three (3) branches, Rating: ≤ 16A @208V

Physical/Environmental
• Dimensions: 70.00" (1778 mm) tall x 2.2" (56 mm) wide x 2.5" (64 mm) deep | Weight: 23 lbs (12.2 kg)
• Shipping Dimensions: 89" x 10" x 5" (226 cm x 25.4 cm x 12.7 cm) | Weight: 24 lbs (12.7 kg)
• Highlight Color: Choose Black, White, Red, Green, Blue, Yellow
• Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2000m elevation
• Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
• Quiescent / Unloaded Power Draw: < 15W for all configurations

Communications and Security
• 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)
• Aux connector for connection of ST Eye® Bluetooth module
• Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) – {also on Link CDU}
• Web-browser GUI and command-line-interface (CLI): HTTP/HTTPS, SSLv3/TLSv1, SSHv2, Telnet, SNMPv2c and v3
(GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP

Certifications
• cTUVus Mark to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07 + A1:2011
• EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
• FCC Class A, Part 15
• RoHS/WEEE

Optional Accessories
• EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m)
• EMCU-1-1B Environmental Monitor adding:
- Two (2) EMTH-1-1 temperature/humidity ports (one probe included)
- One (1) EMWS-1-1 water sensor port (probe sold separately)
- Four (4) dry contact (NO/NC) monitoring points
- One (1) 8-bit analog-to-digital converter (0 to 5VDC)
• KIT-PRO2LINK-01M provides ability to link (2) additional C2X units.
• SPM (Sentry® Power Manager):
- Monitor and manage multiple PDUs from a single point
- Monitor and manage alarm conditions
- Create reports and trends on stored data
- Analyze power usage per phase
- Optional appliance or virtual version
- VMware Ready*
• Mounting Brackets
- Buttons (KIT-0020) included for tool-less mounting (see diagram).
- See the Mounting Bracket Guide for further suggestions.
- Custom mounting options available. Contact your local Server Technology representative.
• Cable Retention Devices for non-locking cords
- EZip
- Cable Sleeve
• Device / Output LockedIn™ Power Cords
- UL Rated, or VDE Rated

Sentry  Cabinet PDU Features

Network Monitoring
The PRO2 hot-swappable network card provides for HTTP(S), SSH, Telnet,SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.

Branch Current Monitoring
PRO2 monitors current at each breaker branch and provides SNMP-based alerts and emails on high usage that risks a tripped circuit.

Star Multi-Linking
PRO2 provides the ability to link up to four power circuits using one IP
address. Primary link provides backup power to network card.

Branch Circuit Protection
PRO2 meets the UL and IEC 60950-1 requirement for branch circuit protection
through use of UL489 rated magnetic-hydraulic circuit breakers.

Hot-Swap Network Card
Network access is ensured when power is lost to the Master unit with
backup power provided by the primary link unit.

ST Eye Bluetooth Ready
The best CDU LCD is the one in your hand. Attach the ST Eye™ Bluetooth
module to PRO2 for access to power data and system settings.

Temperature/Humidity Monitoring
PRO2 Master and Link units each support two external 10' (3m) T/H
probes. Receive SNMP-based alerts and email notifications.

HDOT- High Density Outlet Technology
The highest outlet density available in a network connected PDU.
Meets IEC C13 and C19 specifications, plus high native retention and UL94V-0 flame rating.

Outlet Control
On PRO2 Switched CDUs, cycle power to individual outlets or groups of
outlets to reboot servers. Or, power off unused receptacles.

Alternating Phase
Three phase power is wired in an alternating fashion per outlet for simplified load balancing,
reduced cord lengths, and better airflow.

Auto-flip Current Display
Easy-to-read LEDs display current per phase to help prevent overloads and
simplify three-phase load balancing in high-density cabinets.

Flexible Mounting
PRO2 includes standard button mounts along with provisions for
custom mounting brackets (contact Server Technology for details).

Per-Inlet Power Sensing
Meets ANSI C12.1 for billing-grade accuracy of Current per phase. PIPS
includes voltage, active power, apparent power, power factor, and energy.

High Temperature Rating
This product has been tested and approved for safe and reliable operation
in 60°C (140°F) data center environments.

Color Identification
Choose from six colors to designate circuits for CDUs in the data center.
Color options include Blue, Red, Green, White, Yellow, and Black.

Cisco EnergyWise** Compliant
PRO2 meets the requirements set forth by Cisco System, Inc. for its EnergyWise program for monitoring of device energy.